LC1D65AFE7
TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 115 V AC 50/60 Hz coil
Range: TeSys D Contactors FAQ Documents & Downloads-
Product availability :
Stock - Normally stocked in distribution facility
-
Characteristics
Main range of product TeSys Drange TeSysproduct name TeSys Dproduct or component type Contactordevice short name LC1Dcontactor application Motor controlResistive loadutilisation category AC-4AC-1AC-3poles description 3Ppole contact composition 3 NOSystem Voltage <= 300 V DC power circuit<= 690 V AC 25...400 Hz power circuit[Ie] rated operational current 80 A (<= 140 °F (60 °C)) at <= 440 V AC AC-1 power circuit65 A (<= 140 °F (60 °C)) at <= 440 V AC AC-3 power circuitmotor power kW 11 kW at 400 V AC 50/60 Hz AC-430 kW at 380...400 V AC 50/60 Hz AC-337 kW at 500 V AC 50/60 Hz AC-337 kW at 660...690 V AC 50/60 Hz AC-318.5 kW at 220...230 V AC 50/60 Hz AC-3motor power hp 40 hp at 460/480 V AC 50/60 Hz 3 phases motors5 hp at 115 V AC 50/60 Hz 1 phase motors10 hp at 230/240 V AC 50/60 Hz 1 phase motors20 hp at 200/208 V AC 50/60 Hz 3 phases motors20 hp at 230/240 V AC 50/60 Hz 3 phases motors50 hp at 575/600 V AC 50/60 Hz 3 phases motorscontrol circuit type AC 50/60 Hz[Uc] control circuit voltage 115 V AC 50/60 Hzauxiliary contact composition 1 NO + 1 NC[Uimp] rated impulse withstand voltage Conforming to IEC 60947overvoltage category III[Ith] conventional free air thermal current 80 A at <= 140 °F (60 °C) power circuit10 A at <= 140 °F (60 °C) signalling circuitIrms rated making capacity 1000 A at 440 V power circuit conforming to IEC 60947140 A AC signalling circuit conforming to IEC 60947-5-1250 A DC signalling circuit conforming to IEC 60947-5-1rated breaking capacity 1000 A at 440 V power circuit conforming to IEC 60947[Icw] rated short-time withstand current 100 A 1 s signalling circuit120 A 500 ms signalling circuit140 A 100 ms signalling circuit520 A <= 104 °F (40 °C) 10 s power circuit900 A <= 104 °F (40 °C) 1 s power circuit110 A <= 104 °F (40 °C) 10 min power circuit260 A <= 104 °F (40 °C) 1 min power circuitassociated fuse rating 125 A gG at <= 690 V coordination type 1 power circuit125 A gG at <= 690 V coordination type 2 power circuit10 A gG signalling circuit conforming to IEC 60947-5-1average impedance 1.5 mOhm at 50 Hz - Ith 80 A power circuit[Ui] rated insulation voltage 600 V power circuit certifications CSA600 V power circuit certifications UL690 V power circuit conforming to IEC 60947-4-1690 V signalling circuit conforming to IEC 60947-1600 V signalling circuit certifications CSA600 V signalling circuit certifications ULelectrical durability 1.45 Mcycles 65 A AC-3 at Ue <= 440 V1.4 Mcycles 80 A AC-1 at Ue <= 440 Vpower dissipation per pole 6.3 W AC-39.6 W AC-1protective cover Withmounting support RailPlatestandards CSA C22.2 No 14EN 60947-4-1EN 60947-5-1IEC 60947-4-1IEC 60947-5-1UL 508product certifications CCCULCSAGOSTconnections - terminals Control circuit: screw clamp terminals 2 cable(s) 0...0 in² (1...2.5 mm²) - cable stiffness: flexible - with cable endControl circuit: screw clamp terminals 1 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: flexible - without cable endControl circuit: screw clamp terminals 2 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: flexible - without cable endControl circuit: screw clamp terminals 1 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: flexible - with cable endControl circuit: screw clamp terminals 1 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: solid - without cable endControl circuit: screw clamp terminals 2 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: solid - without cable endPower circuit : screw connection 2 cable(s) 1...25 mm² - cable stiffness: flexible - with cable endPower circuit : screw connection 2 cable(s) 1...25 mm² - cable stiffness: solid - without cable endPower circuit : screw connection 2 cable(s) 1...25 mm² - cable stiffness: flexible - without cable endPower circuit : screw connection 1 cable(s) 1...35 mm² - cable stiffness: solid - without cable endPower circuit : screw connection 1 cable(s) 1...35 mm² - cable stiffness: flexible - without cable endPower circuit : screw connection 1 cable(s) 1...35 mm² - cable stiffness: flexible - with cable endtightening torque Control circuit: 15.04 lbf.in (1.7 N.m) - on screw clamp terminals - with screwdriver flat Ø 6 mmControl circuit: 15.04 lbf.in (1.7 N.m) - on screw clamp terminals - with screwdriver Philips No 2Power circuit: 70.8 lbf.in (8 N.m) - on EverLink BTR screw connectors - cable 0.04...0.05 in² (25...35 mm²) hexagonal 0.16 in (4 mm)Power circuit : 5 N.m - on EverLink BTR screw connectors - cable 1...25 mm² hexagonal 4 mmoperating time 12...26 ms closing4...19 ms openingsafety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1mechanical durability 6 Mcyclesoperating rate 3600 cyc/h at <= 140 °F (60 °C)Complementary coil technology Without built-in suppressor modulecontrol circuit voltage limits 0.3...0.6 Uc drop-out at 140 °F (60 °C), AC 50/60 Hz0.8...1.1 Uc operational at 140 °F (60 °C), AC 50 Hz0.85...1.1 Uc operational at 140 °F (60 °C), AC 60 Hzinrush power in VA 140 VA at 68 °F (20 °C) (cos ϕ 0.75) 60 Hz160 VA at 68 °F (20 °C) (cos ϕ 0.75) 50 Hzhold-in power consumption in VA 13 VA at 68 °F (20 °C) (cos ϕ 0.3) 60 Hz15 VA at 68 °F (20 °C) (cos ϕ 0.3) 50 Hzheat dissipation 4...5 W at 50/60 Hzauxiliary contacts type Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1Type mirror contact (1 NC) conforming to IEC 60947-4-1signalling circuit frequency 25...400 Hzminimum switching current 5 mA signalling circuitminimum switching voltage 17 V signalling circuitnon-overlap time 1.5 ms on de-energisation (between NC and NO contact)1.5 ms on energisation (between NC and NO contact)insulation resistance > 10 MOhm signalling circuitpower range 15...25 kW 200...240 V 3 phases30...50 kW 380...440 V 3 phases30...50 kW 480...500 V 3 phasesmotor starter type Direct on-line contactorcontactor coil voltage 115 V AC standardEnvironment IP degree of protection IP20 front face conforming to IEC 60529protective treatment TH conforming to IEC 60068-2-30pollution degree 3ambient air temperature for operation 23...140 °F (-5...60 °C)ambient air temperature for storage -76...176 °F (-60...80 °C)permissible ambient air temperature around the device -40...158 °F (-40...70 °C) at Ucoperating altitude 9842.52 ft (3000 m) without derating in temperaturefire resistance 1562 °F (850 °C) conforming to IEC 60695-2-1flame retardance V1 conforming to UL 94mechanical robustness Vibrations contactor open 2 Gn, 5...300 HzVibrations contactor closed 4 Gn, 5...300 HzShocks contactor open 10 Gn for 11 msShocks contactor closed 15 Gn for 11 msheight 4.8 in (122 mm)width 2.17 in (55 mm)depth 4.72 in (120 mm)product weight 1.9 lb(US) (0.86 kg)Ordering and shipping details Category 22345 - CTR,D-LINE,OPEN,NONREV-NEWDiscount Schedule I12GTIN 00785901865254Nbr. of units in pkg. 1Package weight(Lbs) 2.0699999999999998Returnability NCountry of origin FROffer Sustainability Sustainable offer status Green Premium productRoHS (date code: YYWW) Compliant - since 0501 - Schneider Electric declaration of conformity Schneider Electric declaration of conformityREACh Product environmental profile AvailableProduct end of life instructions AvailableContractual warranty Warranty period 18 months -
Documents and Downloads (2)
-
Dimensions Drawings
Dimensions(1)Minimum electrical clearanceLC1
D40A…D65A
a
55
b1
with LA4 D●2
–
with LA4 DB3 or LAD 4BB3
136
with LA4 DF, DT
157
with LA4 DM, DW, DL
166
c
without cover or add-on blocks
118
with cover, without add-on blocks
120
c1
with LAD N (1 contact)
–
with LAD N or C (2 or 4 contacts)
150
c2
with LA6 DK10, LAD 6DK
163
c3
with LAD T, R, S
171
with LAD T, R, S and sealing cover
175
-
Connections and Schema
Wiring -
Motor Starter BOM
Our Proposal - Type 1 : Circuit Breaker + Contactor for Motor Power 30 kW and 415 VACMotor power
(kW)
ICU
(kA)
Breaker
Contactor (*)
30
50
GV3P65
LC1D65AFE7Non contractual pictures.
Type 1 coordination requires that in a short-circuit condition, the contactor or starter must not present any danger to personnel or installations and must not be able to resume operation without repair or the replacement of parts.